The PRO-TECH 8505 Battery
Powered Commercial Carbon Monoxide Monitor includes an
electrochemical sensor, continuous digital display, peak level
memory, duration and time of peak level, TWA readout, sensor
life monitor, and manual backlight. Carbon monoxide (CO) levels are sampled and recorded every 5 seconds by a state-of-the-art electrochemical sensor. CO levels detected from 10 to 500 ppm are automatically displayed in the LCD readout. When a chronic carbon monoxide level of 30ppm or more is detected, a flashing Red LED and 85db pulsating alarm are activated. Pressing the reset button temporarily mutes the audible signal while the carbon monoxide level is rechecked. If the monitor continues to detect carbon monoxide levels of 20 ppm or more, the audible and visual alarm signals will reactivate automatically within 5 minutes. If carbon monoxide levels drop below 20 ppm, the alarm signals will not be reactivated. The highest carbon monoxide level detected from 10 to 500 ppm, the duration of the peak level, how long ago the peak occurred, and the average CO level detected for the previous 8 hours can be displayed by pressing the memory button. An internal clock monitors the sensor life and activates visual and audible sensor expiration signals after two years. The Pro-Tech 8505 Commercial Carbon Monoxide Monitor complies with OSHA and NIOSH exposure limits. Backed by a one year limited factory warranty. |
|||||
|
Alarm Basics •
Battery Powered Commercial CO Monitor Certifications/Standards and Warranty
• Complies with OSHA and NIOSH Exposure Limits
|
Alarm Signals
• REL Alarm: 30ppm
≤
7 hrs TWA Display & Memory • Automatic Continuous Display of Current CO Levels from 10-500 ppm• Manually Displays Peak CO Level Detected from 10-500 ppm • Manually Displays Time Duration of Peak CO Level and How Long Ago Occurred • Manually Displays TWA for Previous Eight Hours
*Specifications subject to change without notice. Display accuracy is first year estimate only, and may also be affected by environmental conditions and other circumstances beyond manufacturer's control. This carbon monoxide monitor is not listed or tested to the residential UL 2034 standard. The monitor is intended for use in commercial applications. |
|||||